Troubleshooting module problems using the lcd, Troubleshooting module problems using the lcd -3 – Rockwell Automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTAM) User Manual

Page 83

Advertising
background image

Troubleshooting

9-3

Publication 1747-6.1

Troubleshooting
Module Problems
Using the LCD

TROUBLESHOOTING CONSIDERATIONS

MODULE DISPLAY

COMM LED

PROBABLE CAUSES

RECOMMENDED ACTION

ERROR 100

LED illuminated red

ROM memory failed checksum
test

Reset module.

ERROR 200

LED illuminated red

RAM failed Read/Write test

Reset module.

ERROR 300

LED illuminated red

Keypad malfunction

Reset module.

ERROR 400

LED illuminated red

Configuration memory failed
checksum test

1. Cycle module power.
2. Reconfigure module. Refer

to chapter 3,

Module Setup

Procedure

.

Backlighting off

LED illuminated red

Insufficient power supply
voltage

Check power supply.

Backlighting flashes on and off

LED illuminated red

Insufficient or unregulated
power supply voltage

Check power supply.

LCD background is solid black

Any

Enclosure is too hot

1. Adjust display contrast,

turn pot clockwise.

2. Operate within temperature

specifications.

LCD characters are out of line

Any

Enclosure is too hot or module
is exposed to sudden
temperature change.

Allow temperature to stabilize.

LCD is difficult to read

Any

Backlighting was Turned Off

Reconfigure module. Refer to
chapter 3,

Module Setup

Procedure

.

LCD characters unintelligible

Any

Water contamination in
module

Correct condition.

Improper initialization

Reset module.

Module Cconfigured for a
foreign language

Reconfigure module. Refer to
chapter 3,

Module Setup

Procedure

.

LCD appears faded or no
display at all

Any

Enclosure too cold

Adjust display contrast, turn
pot counter clockwise.

Module subjected to excessive
heat or humidity

Disconnect module. Contact
your local Allen-Bradley
representative.