Chapter

2

Installation and Power Up

Read this chapter before installing the Data Table Access Module. It
describes the procedures for:

• mounting the module

• connecting the module to your system

• module configuration and adjustments

• powering up the module

European Union
Directive Compliance

If this product has the CE mark, it is approved for installation within
the European Union and EEA regions. It has been designed and
tested to meet the following directives.

EMC Directive

This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards,
in whole or in part, documented in a technical construction file:

• EN50081-2

EMC – Generic Emission Standard, Part 2 – Industrial
Environment

• EN50082-2

EMC – Generic Immunity Standard, Part 2 – Industrial
Environment

This product is intended for use in an industrial environment.

Mounting the Module

The module is designed for mounting in a cutout on the door of an
enclosure. The cutout and drilling dimensions for the module are
shown on the following page. We have also included a full-size tear-
out mounting template (appendix D) for your convenience.

When locating the cutout on the enclosure door:

• Provide 139.7 mm (5.5 in) clearance behind the enclosure door

and 50.8 mm (2.0 in) electrical clearance above and below the
module housing.

!

ATTENTION: To keep the module temperature
within the specified range, enclosure temperature must
be between 0 to 55° (32 to 131° F).