Troubleshooting

9-5

Publication 1747-6.1

TROUBLESHOOTING CONSIDERATIONS

GENERAL ERROR SCREEN

ATTEMPTED FUNCTION

PROBABLE CAUSES

RECOMMENDED ACTION

Use a Quick Recall Function

Quick recall function not
defined

Assign an address to that
function.

Quick recall function defined
but that address is not defined
in this processor

Attach to proper node address.

Enter Setup Procedure

Module not in Modify mode

Change module to Modify
mode.

Enter Password

Incorrect password entered

Enter correct password.

Data Address Entry

Incorrect format for address

Reenter address correctly.

Address not defined in this
processor

Allocate address in memory.

Data entry

Module in the Monitor mode

Change module to Modify
mode.

Value out of range for file type

Enter value within range.

Address is read only (input or
output file)

Abort entry.

No response to a function key

Address entry in progress

Complete address entry or
press the

>(6&@

key.

Data entry in progress

Complete data entry or press
the

>(6&@

key.

Illegal Command

Responding to a message

The Data file that the DTAM is
trying to write to does not exist

See your software user
manual for information on how
to create the data entry
destination or acknowledge bit
locations.

Attach to a 5/03 processor

The firmware in the DTAM is
less than revision 3.0 and does
not support 5/03
communications

Verify the firmware revision
number on the DTAM
nameplate, and contact your
local Allen-Bradley sales office
for an upgrade.

Incompat Program

Attach to a processor

The user program in the 5/03
processor is not supported by
DTAM

Abort.

Contact your local Allen-
Bradley sales office.

Illegal Network

LED flashing red

No other nodes are active on
the network

Attach the required processor
to the network.

One or more nodes on the
network have an incorrect
baud rate

Correct the baud rates.

Network is shorted or
improperly wired

Check network cable
connections.

Module has same node
address as a 5/01 or fixed
controller (point-to-point
connection)

Reconfigure the module node
address, refer to chapter 3,

Module Setup Procedure

.

The maximum node address
of the previous node is lower
than the module address

Change the maximum node
address of the previous node.

Duplicate Node

LED flashing red

Module has same node
address as a 5/02 or 5/03
(point-to-point connection)

Change the module node
address.

LED flashing red

Module has same node
address as another node
(DH485 network connect ion)

Change the module node
address.

No Response

LED illuminated green or
flashing green

The node that the module is
attached to has too many other
nodes trying to communicate
with it

Decrease the network traffic to
the desired node address.