Rockwell Automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTAM) User Manual

Page 94

Advertising
background image

9-14

Troubleshooting

Publication 1747-6.1

PROCESSOR ERRORS

Error
Code

Module Display

Fault Description

xx5B

SLOT xx BAD CFG

G file configuration error – User program G file
size exceeds the capacity of the module.

xx5C

SLOT xx BAD CFG

M0-M1 file configuration error – User program
M0-M1 file size exceeds the capacity of the
module.

xx5D

SLOT xx SI/O ERR

Interrupt service requested is not supported by
the processor.

xx5E

SLOT xx SI/O ERR

Processor I/O driver (software) error.

xx60 thru
xx6F

SLOT xx SI/O ERR

Identifies an I/O card specific recoverable
major error. Refer to the user information
supplied with the card for further details.

xx70 thru
xx7F

SLOT xx SI/O ERR

Identifies an I/O card specific non-recoverable
major error. Refer to the user information
supplied with the card for further details.

xx80 thru
xx8F

SLOT xx SI/O ERR

Identifies an I/O card specific non-recoverable
major error. Refer to the user information
supplied with the card for further details.

xx90

SLOT xx MOD ERROR

Interrupt problem at the specified disabled slot.

xx91

SLOT xx MOD ERROR

The specified disabled slot has faulted.

xx92

SLOT xx INT ERROR

Invalid or non-existent module interrupt.

xx93

SLOT xx MOD ERROR

Unsupported I/O module specific major error.

xx94

MOD IN SLOT xx

In the processor run or test mode, a module
has been detected as being inserted under
power. Code xx94 also can mean that an I/O
module reset itself.

Advertising