9-4

Troubleshooting

Publication 1747-6.1

Troubleshooting
Communication
Problems Using the
LCD

TROUBLESHOOTING CONSIDERATIONS

GENERAL ERROR SCREEN

ATTEMPTED FUNCTION

PROBABLE CAUSES

RECOMMENDED ACTION

Attach to node

Illegal node address entered

Node address must be within
the range of 0 through 31.

Change processor to Run
mode

Module not attached to node

Attach to proper node address.

Module not in Modify mode

Change module to Modify
mode.

Display fault

Module not attached to node

Attach to proper node address.

Clear fault

Module not attached to node

Attach to proper node address.

Module not in modify node

Change module to Modify
mode.

Change processor to Program
mode

Module not attached to node

Attach to proper node address.

Module not in Modify mode

Change module to Modify
mode.

EEPROM to RAM memory
transfer

Module not attached to node

Attach to proper node address.

Module not in Modify mode

Change module to Modify
mode.

Processor in Run orTest mode

Change processor to Program
mode.

RAM to EEPROM memory
transfer

Module not attached to node

Attach to proper node address.

Module not in Modify node

Change module to Modify
mode.

Processor in Run, Test or Fault
mode

Change processor to Program
mode or clear fault.

Processor contains no user
program

Download a user program to
processor from a programming
device or HHT.