Troubleshooting

Publication 1747-6.1

Troubleshooting MSG
Instruction Error
Codes

When an error condition occurs with a Message Instruction (MSG),
the error code and its description are indicated in the Data Monitor
display.

INSTRUCTION ERRORS

Error
Code

Fault Description

02H

Target node is busy. The MSG instruction will automatically reload. If other
messages are waiting, the message is placed at the bottom of the stack.

03H

Target node cannot respond because message is too large.

04H

Target node cannot respond because it does not understand the command
parameters OR the control block may have been inadvertently modified.

05H

Local processor is offline (possible duplicate node situation).

06H

Target node cannot respond because requested function is not available.

07H

Target node does not respond.

08H

Target node cannot respond.

09H

Local modem connection has been lost.

10H

Target node cannot respond because of incorrect command parameters or
unsupported command.

11H

Local file has constant file protection.

12H

Local channel configuration protocol error exists.

13H

Local MSG configuration error in the Remote MSG parameters.

14H

Local communication driver is incompatible with the MSG instruction.

15H

Local channel configuration parameter error exists.

16H

Target or Local Bridge address is higher than the maximum node address.

17H

Local service is not supported.

18H

Broadcast (Node Address 155) is not supported.

19H

Improperly formatted Logical ASCII Address string. String not properly
terminated with a NULL character or the string length does not match the
value in the length parameter.

20H

PCCC Description: Host has a problem and will not communicate.

30H

PCCC Description: Remote station host is not there, disconnected, or shut
down.

37H

Message timed out in local processor.

38H

Message disabled pending link response.

40H

PCCC Description: Host could not complete function due to hardware fault.

50H

Target node is out of memory.

60H

Target node cannot respond because file is protected.

70H

PCCC Description: Processor is in Program mode.

80H

PCCC Description: Compatibility mode file missing or communication zone
problem.

90H

PCCC Description: Remote station cannot buffer command.

B0H

PCCC Description: Remote station problem due to download.

C0H

PCCC Description: Cannot execute command due to active IPBs.

D0H

No IP address configured for the network, -or-
Bad command – unsolicited message error, -or-
Bad address – unsolicited message error, -or-
No privilege – unsolicited message error.