Remove and install the power terminal block, 400 and 600 terminals – Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual

Page 48

Advertising
background image

48

Publication 2711P-UM001J-EN-P - November 2009

Chapter 3 Power Connections

Remove and Install the
Power Terminal Block

The terminals are shipped with the power terminal block installed.
You can remove the terminal block for ease of installation, wiring, and
maintenance.

400 and 600 Terminals

Follows these steps to remove the terminal block in the PanelView
400 and 600 terminals.

1. Insert the tip of small, flat-blade, screwdriver into the terminal

block access slot.

WARNING

Explosion Hazard

Substitution of components may impair suitability for hazardous
locations.

Do not disconnect equipment unless power has been switched
off and area is known to be nonhazardous.

Do not connect or disconnect components unless power has
been switched off.

All wiring must comply with N.E.C. articles 501, 502, 503,
and/or C.E.C. section 18-1J2 as appropriate.

Peripheral equipment must be suitable for the location in which
it is used.

ATTENTION

Disconnect all power before installing or replacing components.
Failure to disconnect power may result in electrical shock or
damage to the terminal.

ATTENTION

The AC and DC terminal blocks are keyed and marked
differently so be sure to follow markings. Do not force terminal
blocks into connectors to prevent potential damage to terminal.