Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013

Chapter 6

Terminal Connections

Serial Connections

The RS-232 serial port is multi-purpose and supports these connections:

DH-485 communication through a serial connection
DF1 full-duplex communication with controllers by using direct

connections or modem connections

Third-party point-to-point communication
Application transfers and printing

The serial port is a 9-pin, male, RS-232 connector.

Table 66

shows the pinout

descriptions and how these pins map to the serial ports on the controllers.

The maximum cable length for serial communication is 15.24 m (50 ft).

Figure 16 - RS-232 Serial Port

1

5

6

9

Insert plastic tie wrap in the hole and

use as strain relief for all attached
cables.

Table 66 - RS-232 Serial Port Connector Pinout

PanelView Plus 6 RS-232 Port

9-pin DCE

SLC or Logix

9-pin

PLC
25-pin

MicroLogix/
ENI 8-pin DIN

1

2

2

3

4

3

3

2

7

4

4

20

5

5

7

2

6

6

6

7

7

4

8

8

5

9

Connector Shell

Chassis Gnd

WARNING: Do not connect or disconnect the communication cable with power
applied to the terminal, or the serial device on the other end of the cable. An
electrical arc could cause an explosion in hazardous location installations. Be
sure that power is removed or the area is nonhazardous before proceeding.

RXD

TXD

DTR

COM

DSR

RTS

CTS