60

Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013

Chapter 3

Configuration Mode

Configure a Device Address

Follow these steps to edit the address of a device such as a logic controller.

1. From the RSLinx Configuration dialog box, select a device node.

2. Press Edit Device to view the device name and current address.

3. Press Device Address to modify the address.

The input panel opens with the current address.

4. Use the Input Panel to modify the address and then press Enter.

You return to the previous dialog box with the new address.

5. Press OK.

Modified settings do not take effect until the terminal is restarted.

Ethernet Network
Connections

The terminal has a built-in Ethernet driver. You can configure this Ethernet
information for your terminal:

IP address of terminal on network including link speed
Device name to identify terminal on network
Username and password to access network resources

Set the Ethernet IP Address for the Terminal

Some networks automatically assign IP addresses to Ethernet devices if DHCP is
enabled. If DHCP is not enabled, you can manually enter an IP address.

IMPORTANT

FactoryTalk View ME Station does not recognize an installed 2711P-RN20
Ethernet module. View and manually configure the module’s IP address from
the control panel by using Network and Dial-up Connections.