Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013

149

Terminal Connections

Chapter 6

Software and Firmware Requirements

The software and firmware must be installed on the development computer and
the PanelView Plus 6 terminal to configure and communicate with an
Allen-Bradley controller on a ControlNet network.

Table 72 - ControlNet Unscheduled Communication

Software/Firmware

Minimum Version

FactoryTalk View Studio

6.0 or later

FactoryTalk View Machine Edition Runtime

6.0 or later

ControlNet module firmware

2711P-RN15S, Series A, Rev A (firmware revision 2.07 or
later)

(1)

(1) This applies to terminals that are ordered as pre-configured units with the ControlNet module.

Table 73 - ControlNet Scheduled Communication

Requirements

Minimum Version

FactoryTalk View Studio

6.0 or later

FactoryTalk View Machine Edition Runtime

6.0 or later

RSNetWorx

for ControlNet

5.11 or later

Studio 5000

21.00.00 or later

ControlNet module firmware

2711P-RN15S, Series A, Rev C (firmware revision 3.08 or
later)

(1)

(1) This applies to terminals that are ordered as preconfigured units with the ControlNet module.

WARNING: The ControlNet communication module, cat. no. 2711P-RN15S or
2711P-RN15SK, does not run with FactoryTalk View ME firmware revision
3.20.04 or earlier. All ControlNet modules with revision 3.07 firmware must be
upgraded to revision 3.08 or later; otherwise, outputs can turn on an
indeterminate state.