Overview

Chapter 1

Operator Input

All 700 to 1500 display modules have TFT color, graphic displays with either
keypad, touch screen, or combination keypad/touch-screen input. Common
features and firmware provide for easy migration to a larger display:

Eight-wire resistive touch screens are extremely accurate for operator

interfaces. When a point on the touch screen is pressed, the layers connect
and change the electrical current, which is then registered and processed.

All keypad or combination keypad/touch-screen displays are similar except

for the number of functions keys.

To meet the requirements of specific environmental conditions, high-bright
displays, marine-certified displays, and conformal-coated displays are also
available. Plus, you can order field replaceable bezels.

5

1

2

1

2

4

3

ATTENTION: Use a finger or gloved finger to operate the keypad. To operate the
touch screen, use a finger, gloved-finger or plastic stylus with a minimum tip
radius of 1.3 mm (0.051 in.). Using any other object or tool can damage the
keypad or touch screen.

ATTENTION: Do not carry out multiple operations simultaneously. Doing so can
result in unintended operation:

Touch only one operating element on the screen with one finger at one time.
Press only one key on the terminal at one time.

Table 9 - Display Features

Item

Feature

Description

1

Replaceable ID Label

Product identification label can be replaced with custom label.

2

Display

Analog resistive touch screen applies to touch-screen or combination
keypad/touch-screen terminals.

3

Numeric keypad

0…9, –, Backspace, Enter, Left and Right tab, Shift, Esc, Ctrl, Alt keys.

4

Navigation keys

Use arrow keys for navigation. Use Alt+arrow to initiate these functions:
Alt+left arrow (Home), Alt+right arrow (End)
Alt+up arrow (Page Up), Alt+down arrow (Page Down)

5

Function keys
700 F1

…F10,

K1…K12

1000

F1 …F16, K1…K16

1250

F1 …F20, K1…K20

1500

F1 …F20, K1…K20

Keys that can be configured in the application to perform operations. For
example, F1 can be configured to navigate to another screen.
Replaceable legends are available to customize the function key labels.