Dh-485/dh+ communication module, Status indicators – Rockwell Automation 2711P-xxxx PanelView Plus 6 Terminals User Manual User Manual

Page 145

Advertising
background image

Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013

145

Terminal Connections

Chapter 6

DH-485/DH+ Communication
Module

700 to 1500 terminals with a catalog number 2711P-RN6 or 2711P-RN6K
communication module support communication with these networks:

DH+ networks
DH-485 networks

The communication module has a separate port for each communication
protocol. You can communicate with one network only at one time.

Figure 19 - DH-485/DH+ Communication Module Connectors

Status Indicators

The module has indicators that show the status of the DH-485 or DH+ network
connection.

IMPORTANT

See your controller documentation for appropriate controller connections.

Table 70 - DH-485 and DH+ Status Indicators

Indicator State

Description

Off

Channel is not online.

Blinking green

Device is only node on the network.

Solid green

Device is online and receiving token.

Blinking red

DH-485: Duplicate node.
DH+: Parity error.

Solid red

Failed selftest.

Allen

Bradley

DH-485

1

2
3
4
5

6

2

1

DH+

DH+

3. Blue
2. Shield/Drain
1. Clear

1. Earth/Ground
2. Shield/Drain
3. Signal Ground
4. Channel B
5. Channel A
6. Termination Resistance

Status Indicator

For DH+ communication, use a Belden
9463 twin axial or equivalent cable, cat.
no. 1770-CD.

Advertising