Chapter 2

Install Terminal

North American Hazardous Location Approval

The following information applies when operating this equipment in
hazardous locations.

Informations sur l’utilisation de cet équipement en environnements
dangereux.

When marked, these products are suitable for use in "Class I,
Division 2, Groups A, B, C, D"; Class I, Zone 2, Group IIC, Class II,
Division II, Groups F, G; Class III hazardous locations and
nonhazardous locations only. Each product is supplied with
markings on the rating nameplate indicating the hazardous
location temperature code. When combining products within a
system, the most adverse temperature code (lowest "T" number)
may be used to help determine the overall temperature code of the
system. Combinations of equipment in your system are subject to
investigation by the local Authority Having Jurisdiction at the time
of installation.

Lorqu'ils sont marqués, ces produits ne conviennent qu'à une
utilisation en environnements Classe I, Division 2, Groupes A, B, C
et D ; Classe I, Zone 2, Groupe IIC, Classe II, Division II, Groupes F et
G ; Classe III, dangereux ou non dangereux. Chaque produit est
livré avec des marquages sur sa plaque d'identification qui
indiquent le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés dans un
système, le code de température le plus défavorable (code " T " le
plus faible) peut être utilisé pour déterminer le code de
température global du système. Les combinaisons d'équipements
dans le système sont sujettes à inspection par les autorités locales
qualifiées au moment de l'installation.

WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power has been removed

or the area is known to be nonhazardous.

Do not disconnect connections to this equipment unless

power has been removed or the area is known to be
nonhazardous.

Substitution of components may impair suitability for Class I,

Division 2.

Peripheral equipment must be suitable for the location in

which it is used.

The battery or real-time clock module in this product must

only be changed in an area known to be nonhazardous.

All wiring must be in accordance with Class I, Division 2, Class

II, Division 2, or Class III, Division 2 wiring methods of Articles
501, 502 or 503, as appropriate, of the National Electrical Code
and/or in accordance with Section 18-1J2 of the Canadian
Electrical Code, and in accordance with the authority having
jurisdiction.

AVERTISSEMENT : RISQUE D’EXPLOSION
Couper le courant ou s'assurer que l'environnement est

classé non dangereux avant de débrancher l'équipement.

Couper le courant ou s'assurer que l'environnement est

classé non dangereux avant de débrancher les connecteurs.

La substitution de composants peut rendre cet équipement

inadapté à une utilisation en environnement de Classe I,
Division 2

Les équipements périphériques doivent s'adapter à

l'environnement dans lequel ils sont utilisés.

La batterie ou le module de l'horloge en temps réel de ce

produit doit être changé(e) uniquement dans un
environnement classé sans risque.

Tous les systèmes de câblage doivent être de Classe I,

Division 2, Classe II, Division 2, ou Classe III, Division 2,
conformément aux méthodes de câblage indiquées dans
les Articles 501, 502 ou 503 du National Electrical Code
(Code Electrique National) et/ou conformément à la Section
18-1J2 du Canadian Electrical Code (Code Electrique
Canadien), et en fonction de l'autorité de jurisdiction.

Table 29 - Temperature Codes - PanelView Plus 6 Terminals

Terminal Model

Input Power

Temperature Code

Description

400 and 600 terminals

DC

T4

Do not install terminals rated T4 in environments where atmospheric gases have ignition
temperatures less than 135 °C (275 °F).

AC

T4

700 to 1500 terminals

DC

T4

AC

T3

Do not install terminals rated T3 in environments where atmospheric gases have ignition
temperatures less than 200 °C (392 °F).