2 - install terminal, Chapter 2, Install terminal – Rockwell Automation 2711P-xxxx PanelView Plus 6 Terminals User Manual User Manual

Page 27: Chapter

Advertising
background image

Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013

27

Chapter

2

Install Terminal

Topic

Page

Required Circuit Parameters for USB Peripheral Devices

29

Mounting Clearances

30

Panel Guidelines

30

Panel Cutout Dimensions

30

Remove and Install the Power Terminal Block

37

Mount the 400/600 Terminal in a Panel

33

Mount the 700 to 1500 Terminal in a Panel

35

Remove and Install the Power Terminal Block

37

DC Power Connections

38

AC Power Connections

41

Initial Startup

43

Reset the Terminal

43

ATTENTION: Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined
in IEC 60664-1), at altitudes up to 2000 m (6561 ft) without derating.

The terminals are intended for use with programmable logic controllers. Terminals that are AC powered must be connected to the
secondary of an isolating transformer.

This equipment is considered Group 1, Class A industrial equipment according to IEC CISPR 11. Without appropriate precautions, there
may be difficulties with electromagnetic compatibility in residential and other environments due to conducted or radiated
disturbances.

Korean Radio Wave Suitability Registration - When so marked this equipment is registered for Electromagnetic Conformity
Registration as business equipment (A), not home equipment. Sellers or users are required to take caution in this regard.

This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those
specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from
accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. The terminals meet specified
NEMA, UL type, and IEC ratings only when mounted in a panel or enclosure with the equivalent rating. Subsequent sections of this
publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain
product safety certifications.

In addition to this publication, see the following:

Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1

, for additional installation requirements

NEMA Standards 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different

types of enclosure