Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013

147

Terminal Connections

Chapter 6

DH+ Network Connections

Use a Belden 9463 twin-axial or equivalent cable, catalog number 1770-CD, to
connect a terminal to a DH+ link.

You can connect a DH+ link in two ways:

• Trunk line/drop line - from the drop line to the connector screw

terminals on the DH+ connectors of the processor.

• Daisy chain - to the connector screw terminals on the DH+ connectors

on the processor.

Follow these guidelines when installing DH+ communication links:

Do not exceed these cable lengths:

Trunk line-cable length: 3,048 m (10,000 ft)
Drop-cable length: 30.4 m (100 ft)
The maximum cable length is determined by the baud rate.

Do not connect more than 64 stations on a single DH+ link.

Figure 23 - Terminal Connection to DH+ Link

700 TO 1500 Terminal with

DH-485/DH+ Communication Module

82

Ω terminating resistor for

230.4 Kbps

150

Ω terminating resistor for

57.6 Kbps and 115.2 Kbps

To Controller

Terminating Resistor

DH+ Port on Communication Module

Clear 1

Shield SH 2

Blue 3

Belden