Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013

163

Troubleshooting

Chapter 8

Check the Start-up Messages and Codes

Refer to Start-up Messages and Codes on page 164

for a list of message states and

error codes that can appear on the splash screen during startup.

Check Voltages and Temperatures

Check the battery voltage, processor temperature, and display temperature.

Check the System Event Log

Check the system event log for errors or unexpected behaviors:

From FactoryTalk View ME Station Configuration mode, press Terminal

Settings>System Event Log. Refer to

View and Clear the System Event

Log on page 76

.

From the control panel, open the Hardware Monitor and click the System

Event Log tab. Refer to

System Event Log on page 93

.

Table 79 - Checking Voltage and Temperature Conditions

Check for These Conditions

Where

What to Do

Battery voltage

< 2.75V DC

From terminal desktop: Refer

to

Battery Voltage on page 94

From FactoryTalk View ME Station

Configuration mode:
Refer to

View Terminal Information

on page 76

Replace the battery if needed.

CPU temperature

>95 °C (203 °F)

From terminal desktop: Refer

to

Temperatures on page 94

From FactoryTalk View ME Station

Configuration mode:
Refer to

View Terminal Information

on page 76

Check for obstructed airflow in
the chassis and attempt to
moderate the ambient
temperatures within the
enclosure and surroundings.

Display temperature

>55 °C (131 °F)

From terminal desktop: Refer

to

Temperatures on page 94

:

From FactoryTalk View ME Station

Configuration mode:
Refer to

View the Display

Temperature on page 67