Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013

Chapter 2

Install Terminal

Connect DC Power

Follow these steps to connect the terminal to DC power.

1. Verify that the terminal is not connected to a power source.

2. Strip 7 mm (0.28 in.) of insulation from the ends of the wires.

3. Secure the DC power wires to the marked terminals (+ and –) on the

power terminal block.

4. Secure the earth/ground wire.

On 400 and 600 terminals, secure the earth/ground wire to the

functional earth/ground terminal on the power terminal block.

On 700 to 1500 terminals, secure the earth/ground wire to the

functional earth screw on the back of the display.

5. Apply power to the terminal.

WARNING: Explosion Hazard
Do not disconnect equipment unless power has been switched off and area is
known to be nonhazardous.

Disconnect all power before installing or replacing components. Failure to
disconnect power can result in electrical shock or damage to the terminal.

7 mm

20 mm

+

Earth/Ground to Ground Bus

DC - DC+

GND

DC+

DC –

Functional Earth to Ground Bus

400 or 600 Terminal

700 to 1500 Terminal