Install Terminal

700 to 1500 Terminals

Follow these steps to remove the terminal block from a 700 to 1500 terminal.

1. Loosen the two screws that secure the terminal block.

2. Gently pull the terminal block away from the connector.

Follow these steps to install the terminal block.

1. Reattach the terminal block to the connector until seated.

2. Tighten the two screws that secure the terminal block to a torque of

0.40…0.51 N•m (3.5…4.5 lb•in).

DC Power Connections

Terminals with an integrated 24V DC power supply have these power ratings.

The power supply is internally protected against reverse polarity. Connecting
DC+ or DC- to the earth/ground terminal can damage the device.

External Power Supply

Use a dedicated 24V DC, safety extra-low voltage (SELV) or protective
extra-low voltage (PELV) power supply to power each PanelView Plus 6 device.

Three-position

AC Terminal Block

Two-position

DC Terminal Block

Table 37 - DC Power Ratings

Terminal

Power Supply

Input Voltage

Power Consumption

400, 600

Nonisolated

24V DC nom (18…30V DC)

15 W max (0.6 A at 24V DC)

700 to 1500

Isolated

24V DC nom (18…32V DC)

70 W max ((2.9 A at 24V DC)

ATTENTION: Applying an AC power source to a terminal with a DC power input
can damage the device.

ATTENTION: Use a SELV or PELV power supply as required by local wiring codes
for your installation. These power supplies provide protection so that under
normal and single fault conditions, the voltage between conductors and earth
ground does not exceed a safe value.

TIP

Terminals with an isolated DC power supply can be powered by the same
power source as other equipment, such as a DC power bus.