Publication GMSI10-UM025C-EN-P - August 2010

94 DeviceNet Objects

Identity Object
(Class ID 01

H

)

The Identity Object provides identification and general information about the
device.

Class Attributes

The Identity Object provides no class attributes.

Instance Attributes

Status

The Status is a 16 bit value. The following bits are implemented.

Table C.1 Identity Object Instance Attributes

Attr ID

Access
Rule

Name

Data Type

Default Value

1

Get

Vendor ID

UINT

668 = Entek

2

Get

Device Type

UINT

109 (Specialty I/O)

3

Get

Product Code

UINT

39 (0x27) XM-160
40 (0x28) XM-161
41 (0x29) XM-162

4

Get Revision:

Major
Minor

STRUCT OF
USINT
USINT

Value varies with each firmware revision.
Value varies with each firmware revision.

5

Get

Status

WORD

6

Get

Serial Number

UDINT

7

Get Product

Name

SHORT_
STRING

"XM-160 Overall Vibration Module"
"XM-161 Overall Vibration Module"
"XM-162 Overall Vibration Module"

Table C.2 Identity Object Status

Bit

Name

Description

0

Owned

TRUE indicates that the module has an owner. More
specifically, the Predefined Master/Slave Connection Set
has been allocated to a master.

1

Reserved, set to 0

2

Configured

This bit is set whenever a saved configuration is
successfully loaded from non-volatile memory. This bit is
cleared whenever the default configuration is restored or
loaded.

Advertising