Rockwell Automation 1440-VDRP06-00RH XM-160/161/162 Direct Vibration Module User Manual

Page 99

Advertising
background image

Publication GMSI10-UM025C-EN-P - August 2010

DeviceNet Information 91

• The ADR scanner can not download the configuration data to an XM

module if the module has a saved configuration in its non-volatile
memory. This happens because the saved configuration is restored and
the module enters Run mode when the power is cycled. (Configuration
parameters cannot be downloaded while an XM module is in Run
mode.) XM modules must be in Program mode for the ADR
configuration to be downloaded and this occurs only when there is no
saved configuration.

• An XM module will enter Run mode automatically after the ADR

scanner restores the module’s configuration only if the module is in Run
mode at the time the configuration is saved to the scanner. If the
module is in Program mode when the configuration is saved, then the
module will remain in Program mode after the configuration is
downloaded by the ADR scanner.

• The ADR scanner saves and restores only the configuration parameters

contained in the module’s EDS file. Some XM parameters are not
included in the EDS file because they are not supported by either the
EDS specification or the tools that read the EDS files, for example
RSNetWorx for DeviceNet. These configuration parameters will not be
restored with ADR.

Below is a list of the configuration parameters that are not included in
the EDS file and can not be saved or restored with ADR.

Channel Name
Tachometer Name
Alarm Name
Relay Name
All Triggered Trend related parameters (see page 71)

TIP

To delete a saved configuration from non-volatile
memory, use the Delete service in RSNetWorx for
DeviceNet or perform the following steps in the XM
Serial Configuration Utility.

1. Save the current configuration to a file. From the

File menu, click Save As and enter a file name for
the configuration.

2. Reset the module to factory defaults. Click the

Module tab and click the Reset button.

3. Reload the saved configuration. From the File

menu, click Open and select the configuration file.

4. Make certain to disable auto save. From the Device

menu, clear the Auto Save Configuration check
mark.