Publication GMSI10-UM025C-EN-P - August 2010

68 Configuration Parameters

Sets the relay activation logic.

A or B - Relay is activated when either Alarm A or

Alarm B meets or exceeds the selected Alarm
Status
condition(s).

A and B - Relay is activated when both Alarm A

and Alarm B meet or exceed the selected Alarm
Status
condition(s).

A Only - Relay is activated when Alarm A meets

or exceeds the selected Alarm Status
condition(s).

Options: A only

A or B
A and B

Sets the alarm(s) that the relay will monitor. The
alarm must be from the same device as the relay.
When the Activation Logic is set to "A and B" or "A
or B," you can select an alarm in both Alarm A and
Alarm B. The system monitors both alarms. When
the Activation Logic is set to "A Only," you can
select an alarm only in Alarm A.

Options: Alarm 1

Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6

Note: You can only select an alarm
that is enabled.

Sets the alarm conditions that will cause the relay to
activate. You can select more than one.

Normal - The current measurement is not within

excess of any alarm thresholds.

Alert - The current measurement is in excess of

the alert level threshold(s) but not in excess of the
danger level threshold(s).

Danger - The current measurement is in excess of

the danger level threshold(s).

Disarm-The alarm is disabled or the device is in

Program mode.

Xdcr Fault - A transducer fault is detected on the

associated transducer.

Module Fault - Hardware or firmware failure, or

an error has been detected and is preventing
proper operation of the device.

Options: Normal

Danger
Xdcr Fault
Alert
Disarm
Module Fault

Check to enable.
Clear to disable.

Relay Installed

Indicates whether the relay is a physical relay on a
module or a virtual relay. If the relay is a physical
relay, then you can set the Failsafe parameter.

If the relay is a virtual relay, the Failsafe parameter
is not used or it is disabled.

Relay Parameters

Parameter Name

Description

Options/Comments

XM Configuration
Utility

EDS File

Activation Logic

Logic

XM Configuration
Utility

EDS File

Alarm A/B

Alarm
Identifier
A/B

XM Configuration
Utility

EDS File

Alarm Status to
Activate On

Alarm Levels

XM Configuration
Utility

EDS File

Check = Physical
Relay

Installed =
Physical Relay

Clear = Virtual Relay Not Installed =

Virtual Relay