Instances, Instance attributes, Instances instance attributes – Rockwell Automation 1440-VDRP06-00RH XM-160/161/162 Direct Vibration Module User Manual

Page 120

Advertising
background image

Publication GMSI10-UM025C-EN-P - August 2010

112 DeviceNet Objects

Instances

There are 6 instances of this object.

Instance Attributes

Table C.26 Alarm Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

3

Get

Alarm Status

3 BITS

The current status of the
alarm.

0 = Normal
1 = Alert (alarm)
2 = Danger (shutdown)
3 = Disarm
4 = Xdcr Fault
5 = Module Fault

4

Get/Set

Alarm Enable

BOOL

Indicates whether this
alarm object is enabled.

0 = Disabled
1 = Enabled

6

Get

Threshold Units

USINT

Indicates whether the
threshold and hysteresis
value are specified in
units of measure. Not
applicable to vector
alarms.

Set to 1
1 = Measurement units

7

Get/Set

Condition

USINT

Indicates on which side of
the threshold values the
alarm and danger
conditions exist.

0 = Greater than
1 = Less than
2 = Inside range
3 = Outside range

8

Get/Set

Alert Threshold
(High)

REAL

The threshold value for
the alert (alarm) condition
(greater threshold for
range types).

9

Get/Set

Danger Threshold
(High)

REAL

The threshold value for
the danger (shutdown)
condition (greater
threshold for range types).

10

Get/Set

Alert Threshold
Low

REAL

The lesser threshold value
for the alert (alarm)
condition for the range
condition types.

11

Get/Set

Danger Threshold
Low

REAL

The lesser threshold value
for the danger (shutdown)
condition for the range
condition types.

12

Get/Set

Hysteresis

REAL

The amount on the safe
side of a threshold by
which the value must
recover to clear the alarm.