Publication GMSI10-UM025C-EN-P - August 2010

DeviceNet Objects 121

Class Attributes

Instances

There are 6 instances of this object.

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

100

Get/Set

Transducer
Power Type
(Ch1 & Ch2)

USINT

The type of power
supplied to the Ch1 and
Ch2 transducers.

0 = No power supplied
1 = Constant current (IEPE)

101

Get/Set

Buffer Power
Mode

USINT

Indicates whether the
buffer power setting is
determined automatically
or manually.

0 = Manual mode
1 = Auto mode

102

Get/Set

Buffer Power
Manual Mode
Setting

USINT

Determines the manual
setting of the buffer
power.

0 = Negative voltage
1 = Positive voltage

103

Get

Buffer Power
Status

USINT

The actual buffer power
setting.

0 = Negative voltage
1 = Positive voltage

104

Get/Set

IEPE Voltage
Boost

USINT

Determines whether to
use the IEPE voltage boost
feature.

0 = No boost
1 = Boost enabled, auto
2 = Boost enable, constant

105

Get/Set

Transducer
Power Type
(Ch3 & Ch4)

USINT

The type of power
supplied to the Ch3 & Ch4
transducers.

0 = No power supplied
1 = Constant current (IEPE)

106

Get/Set

Transducer
Power Type
(Ch5 & Ch6)

USINT

The type of power
supplied to the Ch5 & Ch6
transducers.

0 = No power supplied
1 = Constant current (IEPE)

Table C.38 Transducer Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

3

Get

DC Bias

REAL

The measured average DC
bias of the transducer
signal in volts.

Volts

4

Get

Status

BOOL

Indicates whether a
transducer fault exists
(the measured DC Bias is
outside the range
specified by Fault High
and Low).

0 = No fault
1 = Transducer fault exists