Configuration Parameters 61

Eng. Units

Defines the native units of the transducer. Your
choice controls the list of possible selections
available in the Output Data Units parameter. It
also affects other module parameters.

Fault Low

The minimum, or most negative, expected DC
voltage from the transducer.

Volts

Note: A voltage reading outside this
range constitutes a transducer fault.

Fault High

The maximum expected DC bias voltage from the
transducer.

DC Bias Time Constant

The time constant used for exponential averaging
(low pass filtering) of the transducer DC bias
measurement. The corner frequency for the low pass
filter is 1 / (2

π

x DC Bias Time Constant). The

greater the value entered, the longer the settling
time of the measured value to a change in the input
signal. See example table below.

Seconds

Channel Transducer Parameters

Parameter Name

Description

Values/Comments

Eng. Units
Options

Quantity of
Measure

g (gravity)

Acceleration

ips (inch per
second)

mm/s
(millimeters per
second)

Velocity

mils (1/1000
inch)

um (micro
meter)

Displacement

Volts

Voltage

Pa (pascals)

psi (pound-force
per square inch)

pressure

Time Constant

(seconds)

-3dB Frequency

(Hz)

Settling

(seconds)

1

0.159

3

2

0.080

6

3

0.053

9

4

0.040

12

5

0.032

15

6

0.027

18

7

0.023

21

8

0.020

24

9

0.018

27

10

0.016

30