Transition to program mode, Transition to run mode, Transition to program mode transition to run mode – Rockwell Automation 1440-VDRP06-00RH XM-160/161/162 Direct Vibration Module User Manual

Page 92

Advertising
background image

Publication GMSI10-UM025C-EN-P - August 2010

84 DeviceNet Information

Transition to Program Mode

Parameter values can only be downloaded to an XM module while the module
is in Program mode. Any attempt to download a parameter value while the
module is in Run mode will result in a Device State Conflict error.

To transition an XM module from Run mode to Program mode on a
DeviceNet network, set the Device Mode parameter to "Program mode" and
click Apply. Note that you cannot change any other parameter until you have
downloaded the Program mode parameter.

Refer to your DeviceNet documentation for specific instructions on editing
EDS device parameters.

Transition to Run Mode

In order to collect data and monitor measurement devices, XM modules must
be Run mode. To transition an XM module from Program mode to Run mode
on a DeviceNet network, set the Device Mode parameter to "Run mode" and
click Apply.

Refer to your DeviceNet documentation for specific instruction on editing
EDS device parameters.

TIP

The Module Status indicator flashes green when the
module is in Program mode.

TIP

You can also use the Stop service described on page 85 to
transition XM modules to Program mode.

TIP

The Module Status indicator is solid green when the
module is in Run mode.

TIP

You can also use the Start service described on page 85 to
transition XM modules to Run mode.