Manually resetting relays – Rockwell Automation 1440-VDRP06-00RH XM-160/161/162 Direct Vibration Module User Manual

Page 64

Advertising
background image

Publication GMSI10-UM025C-EN-P - August 2010

56 Installing the XM-160/161/162 Direct Vibration Module

The device test occurs after the LED test. The Module Status (MS) indicator is
used to indicate the status of the device self-test.

Refer to Module Indicators on page 54 for more information about the LED
indicators.

Manually Resetting Relays

The Direct Vibration modules have an external reset switch located on top of
the module, as shown in Figure 2.47.

Figure 2.47 Reset Switch

The switch can be used to reset all latched relays in the Expansion Relay
module when it is connected to the XM-160, XM-161, or XM-162.

MS Indicator State

Description

Flashing Red and Green

Device self test is in progress.

Solid Green or Flashing Green

Device self test completed successfully, and the
firmware is valid and running.

Flashing Red

• Device self test completed, the hardware is OK, but

the firmware is invalid.

• Firmware download is in progress.
• Module power voltage is incorrect.

Solid Red

Unrecoverable fault, hardware failure, or Boot Loader
program may be corrupted.

IMPORTANT

The Reset switch resets the relays only if the input is no
longer in alarm or the condition that caused the alarm is no
longer present.

1440-VDRx06-0xRH

Press the Reset
Switch to reset the
relays