Iepe buffer power and signal detection parameters – Rockwell Automation 1440-VDRP06-00RH XM-160/161/162 Direct Vibration Module User Manual

Page 66

Advertising
background image

Publication GMSI10-UM025C-EN-P - August 2010

58 Configuration Parameters

IEPE Buffer Power and
Signal Detection
Parameters

Use these parameters to configure the IEPE and buffer power options and to
determine the measurement performed on the input signal to produce the
overall value.

IEPE Buffer Power and Signal Detection Parameters

Parameter Name

Description

Values/Comments

Controls whether to provide standard accelerometer
(IEPE) power to the transducer. The IEPE Power is
configurable in channel pairs: Channels 1 and 2,
Channels 3 and 4, and Channels 5 and 6.

Important: When mixing transducer types, such as
IEPE accelerometers and non-contact sensors,
non-IEPE powered transducers cannot be in a
channel-pair with IEPE transducers. For example, if
you plan to use a single accelerometer and a single
non-contact sensor, wire the accelerometer to
channel 1 and enable IEPE Power Channels 1 and
2
. Wire the non-contact sensor to channel 3 and
disable IEPE Power Channels 3 and 4. See page
49 for wiring details.

Signal Detection

The measurement (or calculation) performed on the
input signal to produce the Overall Value. See Data
Parameters on page 74.

RMS - The Overall Value is the root mean squared

(RMS) signal level of the input signal.

Calculated Peak - The Overall Value is the

measured RMS value multiplied by the square root
of two (1.4142).

Calculated Peak-to-Peak - The Overall Value is

the measured RMS value multiplied by two times
the square root of two (2.8284).

True Peak - The Overall Value is the output of a

peak detector applied to the input signal.

True Peak-to-Peak - The Overall Value is the

output of a peak-to-peak detector applied to the
input signal.

Options: RMS

Calculated Peak
Calculated Peak-to-Peak
True Peak
True Peak-to-Peak

Note: This parameter setting applies
to all six channels.

XM Configuration
Utility

EDS File

Enable IEPE
Power

IEPE Power

XM Configuration
Utility

EDS File

Check to Enable

Enabled

Clear to Disable

Disabled

Advertising