Rockwell Automation 1440-VDRP06-00RH XM-160/161/162 Direct Vibration Module User Manual

Page 32

Advertising
background image

Publication GMSI10-UM025C-EN-P - August 2010

24 Installing the XM-160/161/162 Direct Vibration Module

The XM-161 and XM-162 modules can be wired to a Remote Relay Reset
Signal. To activate the switch, the switch input terminal should be connected
to ground/common. The XM-162 module provides a dedicated terminal for
this purpose. However, the XM-161 module does not. Therefore, the input
terminal must be wired to any of the XM-161 module’s Signal Common or
24V Power Supply GND/COM terminals.

Wire the Remote Relay Reset Signal to the terminal base as shown in
Figure 2.11.

Figure 2.11 Remote Relay Reset Signal Connection

A single switch contact can also be shared by multiple XM modules wired in
parallel as shown in Figure 2.12.

TIP

The XM-160 module does not support a Remote Relay
Reset Signal. The XM-160 relays can be reset using the
reset switch on top of the module, the serial configuration
tool, or a DeviceNet command (see XM Services on
page 85)
.

ATTENTION

If the Relay Reset switch cable exceeds a length of 30m,
then the cable must be shielded with the shield earth
grounded.

ATTENTION

The relay reset connections may be different for different
XM modules. Figure 2.12 applies only to the XM-162
module. Refer to the installation instructions for the
module for its terminal assignments.