Publication GMSI10-UM025C-EN-P - August 2010

Installing the XM-160/161/162 Direct Vibration Module 19

34

No Connection

4-20mA 1...3 V+

GND/COM

XM-161 channel 1, 2, & 3 4-20mA positive voltage supply
input (4-20mA loops returned directly to external power
source)
XM-162 circuit ground (Relay Reset and SetPtMult switch
return)

35

No Connection

4-20mA 1...3 V+

GND/COM

XM-161 channel 1, 2, & 3 4-20mA positive voltage supply
input (4-20mA loops returned directly to external power
source)
XM-162 circuit ground (Relay Reset and SetPtMult switch
return)

36

No Connection

Relay Reset

Relay reset switch input
Switch returned to 24V GND (or signal common)

37

+24V In

Connection to external +24V power supply, positive side

38

24V Common

Connection to external +24V power supply, negative side
(internally DC-coupled to circuit ground)

39

Reserved

40

Common

Internally DC-coupled to circuit ground

41

Chassis

Connection to DIN rail ground spring or panel mounting hole

42

Chassis

Connection to DIN rail ground spring or panel mounting hole

43

Chassis

Connection to DIN rail ground spring or panel mounting hole

44

CAN_High

DeviceNet bus connection, high differential (white wire)

45

CAN_Low

DeviceNet bus connection, low differential (blue wire)

46

CAN Shield

DeviceNet bus connection to chassis ground (bare wire)

47

DNet V (+)

DeviceNet bus power input, positive side (red wire)

48

DNet V (-)

DeviceNet bus power input, negative side (black wire)

49

No Connection

SetPtMult

Switch input to activate Setpoint Multiplier
Switch returned to 24V GND (or signal common)

50

No Connection

4-20mA 4...6 V+

GND/COM

XM-161 channel 4, 5, & 6 4-20mA positive voltage supply
input (4-20mA loops returned directly to external power
source)
XM-162 circuit ground (Relay Reset and SetPtMult switch
return)

51

No Connection

4-20mA 4...6 V+

GND/COM

XM-161 channel 4, 5, & 6 4-20mA positive voltage supply
input (4-20mA loops returned directly to external power
source)
XM-162 circuit ground (Relay Reset and SetPtMult switch
return)

Terminal Block Assignments

Name

No.

XM-160

XM-161

XM-162

Description

Advertising