54 Installing the XM-160/161/162 Direct Vibration Module

2. Make certain the side connector (B) is pushed all the way to the left. You

cannot install the module unless the connector is fully extended.

3. Make sure that the pins on the bottom of the module are straight so they

will align properly with the connector in the terminal base unit.

4. Position the module (D) with its alignment bar (E) aligned with the

groove (F) on the terminal base.

5. Press firmly and evenly to seat the module in the terminal base unit. The

module is seated when the latching mechanism (G) is locked into the
module.

6. Repeat the above steps to install the next module in its terminal base.

Module Indicators

Each Direct Vibration module has eight LED indicators, which include a
module status (MS) indicator, a network status (NS) indicator, and a status
indicator for each channel (CH1 to CH6). The LED indicators are located on
top of the module.

Figure 2.46 LED Indicators

The following tables describe the states of the LED status indicators.

Module Status (MS) Indicator

1440-VDRx06-0xRH

Module Indicators

Color

State

Description

No color

Off

No power applied to the module.

Green

Flashing Red

Module performing power-up self test.

Flashing

Module operating in Program Mode

1

.

Solid

Module operating in Run Mode

2

.

Red

Flashing

• Application firmware is invalid or not loaded.

Download firmware to the module.

• Firmware download is currently in progress.
• The module power voltage is incorrect.

Solid

An unrecoverable fault has occurred. The module may
need to be repaired or replaced.