Rockwell Automation 1440-VDRP06-00RH XM-160/161/162 Direct Vibration Module User Manual

Page 89

Advertising
background image

Publication GMSI10-UM025C-EN-P - August 2010

Specifications 81

Relays

Number

Failsafe

Latching

Time Delay

Voting Logic

Reset

Activation On

Up to eight relays when interconnected to
one or two XM-441 Expansion Relay
modules, or
Eight virtual relays whose status can be
used by remote control systems

Normally energized (failsafe), or
Normally de-energized (non-fail-safe)

Latching, or
Non-latching

0 to 25.5 seconds, adjustable in 100msec
increments

Single or paired “And” or “Or” logic applied
to any alarm

Local reset switch on top of module
Digital reset command via serial or
DeviceNet interface
Remote reset switch wired to terminal base
(XM-161 and XM-162 only)

Alarm Status:

Normal
Alert
Danger
Disarm
Transducer fault
Module fault

Non-Volatile Configuration

A copy of the module configuration is
retained in non-volatile memory from where
it is loaded upon power up*.

*The configuration stored in non-volatile

memory can be deleted only by a module-reset
command sent via the serial interface, using
the Serial Configuration Utility, or via
DeviceNet from any compliant software
application.

Power

Supply Voltage

XM-160 & XM-162 Module

XM-161 Module

+18 to 32V dc

Maximum current: 190mA @ 24V dc
Maximum Power Dissipation: 4.56 Watts @
24 Volts (4.3 Watts @ 18V dc, 4.9 Watts
@32V dc)

Maximum Current: 310mA @ 24V dc
Maximum Power Dissipation: 7.44 Watts @
24 Volts (7 Watts @ 18V dc, 8 Watts @ 32V
dc)

XM-160/161/162 Direct Vibration Technical Specifications

Product Feature

Specification