Publication GMSI10-UM004B-EN-P - May 2010

DeviceNet Objects 99

Services

The settable attributes of this object are not affected by the status of the
Device Mode Object.

1

Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.

8

Get/Set

Alert Threshold
(High)

REAL

The threshold value for
the alert (alarm) condition
(greater threshold for
range types).

9

Get/Set

Danger
Threshold (High)

REAL

The threshold value for
the danger (shutdown)
condition (greater
threshold for range types).

10

Get/Set

Alert Threshold
Low

REAL

The lesser threshold value
for the alert (alarm)
condition for the range
condition types.

11

Get/Set

Danger
Threshold
Low

REAL

The lesser threshold value
for the danger (shutdown)
condition for the range
condition types.

12

Get/Set

Hysteresis

REAL

The amount on the safe
side of a threshold by
which the value must
recover to clear the alarm.

14

Get/Set

Startup Period

UINT

The amount of time that
the Tach Fault status may
be inhibited after the
startup signal is received.

Seconds

18

Get/Set

Name

STRING2

A name to help identify
this alarm.

20

Get/Set

Inhibit Tach
Fault

BOOL

Determines whether the
Tach Fault status is
prohibited during the
startup period.

0 = Tach Fault allowed
1 = Tach Fault inhibited

Table C.29 Alarm Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

Table C.30 Alarm Object Services

Service
Code

Class/Instance Usage

Name

Description

0E

h

Instance

Get_Attribute_Single

Returns a single attribute.

10

h

Instance

Set_Attribute_Single

Sets a single attribute.