Rockwell Automation 1440-SPD02-01RB XM-220 Dual Speed Module User Manual

Page 46

Advertising
background image

Publication GMSI10-UM004B-EN-P - May 2010

38 Installing the XM-220 Dual Speed Module

Connect the DeviceNet cable to the terminal base unit as shown.

The devices are shipped from the factory with the network node address
(MAC ID) set to 63. The network node address is software settable. You can

Connect

To

Terminal

Red Wire

DNet V+

26 (Optional - see note)

White Wire

CAN High

23

Bare Wire

Shield (Chassis)

10

Blue Wire

CAN Low

24

Black Wire

DNet V-

27

IMPORTANT

The DeviceNet power circuit through the XM module
interconnect, which is rated at only 300 mA, is not intended
or designed to power DeviceNet loads. Doing so could
damage the module or terminal base.

To preclude this possibility, even unintentionally, it is
recommended that DeviceNet V+ be left unconnected.

ATTENTION

You must ground the DeviceNet shield at only one
location. Connecting the DeviceNet shield to terminal 10
will ground the DeviceNet shield at the XM module. If you
intend to terminate the shield elsewhere, do not connect
the shield to terminal 10.

ATTENTION

The DeviceNet network must also be referenced to earth at
only one location. Connect DNet V- to earth or chassis at
one of the XM modules.

ATTENTION

The DNet V+ and DNet V- terminals are inputs to the XM
module. Do not attempt to pass DeviceNet power through
the XM terminal base to other non-XM equipment by
connecting to these terminals. Failure to comply may result
in damage to the XM terminal base and/or other
equipment.

IMPORTANT

Terminate the DeviceNet network and adhere to the
requirements and instructions in the ODVA Planning and
Installation Manual - DeviceNet Cable System, which is
available on the ODVA web site (http://www.odva.org).

Advertising