Configuration Parameters 49

DC Bias Time Constant

The time constant used for exponential averaging
(low pass filtering) of the transducer DC bias
measurement. The corner frequency for the low pass
filter is 1 / (2 x

π

x DC Bias Time Constant). See

example table below.

Seconds

Sets the trigger mode. In Auto Trigger mode, the
minimum signal amplitude for triggering is 2 volts
peak-to-peak and minimum frequency is 6 CPM (0.1
Hz).

In Manual Trigger mode, the value entered in
Trigger Threshold is used as the trigger point.
Minimum signal amplitude for triggering is 500
millivolts peak-to-peak and minimum frequency is 1
CPM (0.0167 Hz).

Important: If you are using Auto
Trigger mode with passive magnetic
sensors, make certain to enable the
Bias Current parameter (see page
48). The bias current parameter
adjusts the auto-trigger detection
algorithm for passive magnetic
signals.

Trigger Hysteresis

The amount of hysteresis around the trigger
threshold. In Auto Trigger mode, the value entered is
a percentage of the peak-to-peak input signal. This
value can range from 0 to 50%.

In Manual Trigger mode, the value entered is a
voltage level. The hysteresis voltage is added to or
subtracted from the threshold voltage to determine
the hysteresis range. The minimum value is 0.12
volts.

% in Auto Trigger mode
Volt in Manual Trigger mode

Tachometer Parameters

Parameter Name

Description

Values/Comments

Time Constant

(seconds)

-3dB Frequency

(Hz)

Settling

(seconds)

1

0.159

2.2

2

0.080

4.4

3

0.053

6.6

4

0.040

8.8

5

0.032

11

6

0.027

13.2

7

0.023

15.4

8

0.020

17.6

9

0.018

19.8

10

0.016

22

XM Configuration
Utility

EDS File

Auto Trigger

Trigger
Mode

XM Configuration
Utility

EDS File

Check = Auto Mode

Auto

Clear = Manual
Mode

Manual