Specifications, Appendix a, Appendix – Rockwell Automation 1440-SPD02-01RB XM-220 Dual Speed Module User Manual

Page 73

Advertising
background image

65

Publication GMSI10-UM004B-EN-P - May 2010

Appendix

A

Specifications

The Appendix lists the technical specifications for the XM-220 module.

XM-220 Technical Specifications

Product Feature

Specification

Communications

DeviceNet

Side Connector

Serial

Standard DeviceNet protocol for all
functions

NOTE: The XM-220 uses only the DeviceNet
protocol, not power. Module power is provided
independently.

Available Electronic Data Sheet (EDS) file
provides support for most DeviceNet
compliant systems
Baud rate automatically set by bus master
to 125kb, 250kb, 500kb
Configurable I/O Poll Response message
helps optimize space utilization within
scanner input tables.

Selectable Poll Response Assembly
Selectable Poll Response Size
(bytes)

All XM measurement and relay modules
include side connectors that allow
interconnecting adjacent modules, thereby
simplifying the external wiring
requirements.
The interconnect provides primary power,
DeviceNet communication, and the circuits
necessary to support expansion modules,
such as the XM-441 Expansion Relay
module.

RS-232 via mini-connector or terminal base
unit
Baud rate fixed at 19200.

NOTE: Local configuration via Serial
Configuration Utility.

Advertising