Publication GMSI10-UM004B-EN-P - May 2010

Installing the XM-220 Dual Speed Module 13

Figure 2.6 Grounded DeviceNet V- at XM Module

For more information on the DeviceNet installation, refer to the ODVA
Planning and Installation Manual - DeviceNet Cable System, which is available
on the ODVA web site (http://www.odva.org).

Switch Input Grounding

The Switch Input circuits are functionally isolated from other circuits. It is
recommended that the Switch RTN signal be grounded at a single point.
Connect the Switch RTN signal to the XM terminal base (Chassis terminal) or
directly to the DIN rail, or ground the signal at the switch or other equipment
that is wired to the switch.

Mounting the Terminal
Base Unit

The XM family includes several different terminal base units to serve all of the
measurement modules. The XM-941 terminal base, Cat. No. 1440-TB-B, is the
only terminal base unit used with the XM-220.

To
Ground

Bus

ATTENTION

Use of a separate DeviceNet power supply is not
permitted. See Application Technique "XM Power Supply
Solutions", publication ICM-AP005A-EN-E, for guidance
in using XM with other DeviceNet products.