DeviceNet Objects 103

Services

Setting the attributes of this object are not affected by the status of the Device
Mode Object.

1

Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.

11

Get/Set

Alarm Identifier
B

EPATH

Identifies the second
alarm status the relay
monitors.

See Parameter Object instances
9 to 13.

12

Get/Set

Logic

USINT

Indicates the number of
associated alarms that
must have a status value
specified by Alarm Level
in order to activate the
relay.

0 = Ignore Alarm Identifier B
and activate the relay based on
the status of Alarm Identifier
A
.
1 = Activate the relay if the
status of either Alarm
Identifier A
or B matches any
of the statuses specified by
Alarm Level.
2 = Activate the relay if the
status of both Alarm Identifier
A
and B match any of the
statuses specified by Alarm
Level
.

14

Get

Relay Installed

BOOL

Indicates whether an
actual relay is associated
with this instance.

0 = Not installed
1 = Installed

Table C.34 Relay Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

Table C.35 Relay Object Services

Service
Code

Class/Instance Usage

Name

Description

05

h

Class/Instance

Reset

Resets latched relay(s).

0E

h

Class/Instance

Get_Attribute_Single

Returns a single attribute.

10

h

Class/Instance

Set_Attribute_Single

Sets a single attribute.