Publication GMSI10-UM004B-EN-P - May 2010

Installing the XM-220 Dual Speed Module 21

Figure 2.8 DC Input Power Supply Connections

Connecting the Relays

The XM-220 has both Normally Open (NO) and Normally Closed (NC) relay
contacts. Normally Open relay contacts close when the control output is
energized. Normally Closed relay contacts open when the control output is
energized.

-

24V dc

Power

Supply

+

-

IMPORTANT

A Class 2 circuit can be provided by use of an NEC Class 2
rated power supply, or by using a SELV or PELV rated
power supply with a 5 Amp current limiting fuse installed
before the XM module(s).

IMPORTANT

24Vdc needs to be wired to terminal 44 (+24 V In) to
provide power to the device and other XM modules linked
to the wired terminal base via the side connector.

IMPORTANT

When the XM-220 is used as part of an Electronic
Overspeed Detection System, redundant power may be
applied directly to the module per the XM Electronic
Overspeed Detection System User Guide, publication
GMSI10-UM015A-EN-E.

ATTENTION

The power connections are different for different XM
modules. Refer to the installation instructions for your
specific XM module for complete wiring information.