Rockwell Automation 1440-SPD02-01RB XM-220 Dual Speed Module User Manual

Page 50

Advertising
background image

Publication GMSI10-UM004B-EN-P - May 2010

42 Installing the XM-220 Dual Speed Module

Network Status (NS) Indicator

1

Normal condition when the module is not a slave to an XM-440, PLC, or other master device.

Channel 1 and Channel 2 Indicators

Startup (Start) Indicator

Color

State

Description

No color

Off

Module is not online.

Module is autobauding.

No power applied to the module, look at Module
Status LED.

Green

Flashing

Module is online (DeviceNet) but no connections are
currently established.

1

Solid

Module is online with connections currently
established.

Red

Flashing

One or more I/O connections are in the timed-out state.

Solid

Failed communications (duplicate MAC ID or Bus-off).

Color

State

Description

No color

Off

Normal operation within alarm limits on the channel.

No power applied to the module, look at Module
Status LED.

Yellow

Solid

An alert level alarm condition exists on the channel
(and no transducer fault, tachometer fault, or danger
level alarm condition exists).

Flashing

Tachometer fault (no transducer fault) condition exists
on the channel.

Red

Solid

A danger level alarm condition exists on the channel
(and no transducer fault or tachometer fault condition
exists).

Flashing

A transducer fault condition exists on the channel.

Color

State

Description

Yellow

Off

Startup period is not in effect.

Solid

Startup period is in effect.

Module may be inhibiting the Tach Fault alarm status.

Module may be monitoring for locked rotor
conditions.