62 Configuration Parameters

Locked Rotor Alarm Status

States the current status of the locked rotor alarm.

Possible status values:

Normal - The alarm is enabled, the
device is in Run mode, there is no
transducer fault, and the current
measurement is not within the Alert
or Danger Threshold value(s).

Alert - The alarm is enabled, the
device is in Run mode, there is no
transducer fault or danger condition,
and the measured speed was less
than the Alert Threshold value
when the Alert Period expired.

Danger - The alarm is enabled, the
device is in Run mode, there is no
transducer fault, and the measured
speed was less than the Danger
Threshold
value when the Danger
Period
expired.

Disarm-The alarm is disabled or the
device is in Program mode.

Transducer Fault - The alarm is
enabled, the device is in Run mode,
and the transducer’s DC bias is
outside the transducer’s Fault
High/Fault Low
range.

Tachometer Fault - The alarm is
enabled, the device is in Run mode,
a tachometer fault exists, (and no
transducer fault), and the Alert
Period
has expired.

Module Fault - Hardware or
firmware failure, or an error has
been detected and is preventing
proper operation of the device.

Relay Status

States the current status of the relay.

Possible status values: Activated

Not Activated

Alarm and Relay Status Parameters