Rockwell Automation 1440-SPD02-01RB XM-220 Dual Speed Module User Manual
Page 36
Publication GMSI10-UM004B-EN-P - May 2010
28 Installing the XM-220 Dual Speed Module
Figure 2.16 Remote Relay Reset Signal Connection
A single switch contact can also be shared by multiple XM modules wired in
parallel as shown in Figure 2.17.
Figure 2.17 Typical Multiple XM Modules Remote Relay Reset Signal Connection
ATTENTION
The Switch Input circuits are functionally isolated from
other circuits. It is recommended that the Switch RTN
signal be grounded at a signal point. Connect the Switch
RTN signal to the XM terminal base (Chassis terminal) or
directly to the DIN rail, or ground the signal at the switch
or other equipment that is wired to the switch.
ATTENTION
The relay reset connections may be different for different
XM modules. Figure 2.17 applies only to the XM-220
module. Refer to the installation instructions for the
module for its terminal assignments.