Overview, Installation and alignment, 4 remote test input – Banner EZ-SCREEN Low-Profile Safety Light Curtain Systems User Manual

Page 40: 5 auxiliary (ossd follow/fault) output, 6 preparing for system operation, 7 sensor “swapability” and emitter hookup

Advertising
background image

38

P/N 133487

Banner Engineering Corp.

Minneapolis, U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

Overview

38

P/N 140044 rev.

E

Banner Engineering Corp.

Minneapolis, U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

EZ-SCREEN LP

Instruction Manual

Installation and Alignment

External Device Monitoring Hookup

If not connected previously, it is again strongly recommended

that one normally closed, forced-guided monitoring contact

of each FSD and MPCE be wired as shown in the monitoring

circuit (see Figures 3-24 and 3-26). Pins 2 and 3 of the receiver

connector provide connection for the external device monitoring

input. External device monitoring (EDM) must be wired in

one of three configurations described below and this wiring

configuration must agree with the receiver’s EDM DIP switch

settings (see Section 4.2).
One-Channel Monitoring: This is a series connection of closed

monitor contacts that are forced-guided (mechanically linked)

from each device controlled by the EZ-SCREEN LP. The monitor

contacts must be closed before the EZ-SCREEN LP can be

reset and the OSSDs can turn ON. After a reset is executed

and the safety outputs (OSSDs) turn ON, the status of the

monitor contacts are no longer monitored and may change state.

However, the monitor contacts must be closed within

250 milliseconds of the OSSD outputs going from ON to OFF.

See Figure 3-19.
Refer to Figure 3-26 for 1-channel EDM hookup. Connect the

monitor contacts between +24V dc and EDM1 (pin 3). Leave

EDM2 (pin 2) open (no connection), unless using the Auxiliary

Output feature (Section 3.5.5). Set the configuration DIP switch

to the 1-channel EDM position, per Section 4.2.
Two-Channel Monitoring: This is an independent connection

of closed monitor contacts that are forced-guided (mechanically

linked) from each device controlled by the EZ-SCREEN LP. The

monitor contacts must be closed before the EZ-SCREEN LP can

be reset and the OSSDs can turn ON. Regardless of the state of

the OSSDs, the monitor contacts may change state (either both

open, or both closed). If the monitor contacts remain in opposite

states for more than 250 milliseconds, a lockout will occur.
Refer to Figures 3-24 or 3-26 for 2-channel EDM hookup.

Connect the monitor contacts as shown between +24V dc and

EDM1 (pin 3) and between +24V dc and EDM2 (pin 2). Set the

configuration DIP switch to the 2-channel EDM position, per

Section 4.2.
No Monitoring: Use this configuration initially, in order to

perform the initial checkout; see Section 3.6. If the application

does not require the EDM function, it is the user’s responsibility

to ensure that this configuration does not create a hazardous

situation.
Refer to Figure 3-25 for “no monitoring” hookup. To configure

the EZ-SCREEN LP for no monitoring, connect or jumper EDM1

(pin 3) to EDM2 (pin 2) using the supplied wire-nut. Set the

configuration DIP switch to the 2-channel EDM position, per

Section 4.2.
An alternate method to configure no monitoring is to set the

configuration DIP switch to the 1-channel EDM position, per

Section 4.2, and connect EDM1 (pin 3) to +24V dc. This method

allows the use of the auxiliary output (see Section 3.5.5) in

applications that do not require the EDM function.

3.5.4 Remote Test Input

An emitter connection is provided (Test) for the connection of an

external remote test switch (typically a normally open contact

held closed). Opening this switch “turns OFF” the emitter,

simulating an interruption of the light beams; all OSSD outputs

will turn OFF. This input is used in conjunction with the emitter

Test/Reset DIP switch. See Sections 2.7.2, 4.2, and Figure 3-23.

3.5.5 Auxiliary (OSSD Follow/Fault) Output

EZ-SCREEN LP receivers have an auxiliary status output that

provides a PNP current-sourcing output (250 mA max.) that

mirrors the state of the OSSDs or indicates a lockout (ON =

Fault). The output is on pin 2 (orange/black wire) when the

EDM configuration DIP switch is set to the 1-channel monitoring

position, per Section 4.2. See the 1-channel EDM circuit on

Figure 3-26 for hookup information.
To use the auxiliary output in an application configured for no

monitoring, set the configuration DIP switch to the 1-channel

monitoring position, per Section 4.2, and connect EDM1 (pin 3)

to +24V dc (see Section 3.5.3).
The emitter also has a Fault output that can be enabled to

indicate the emitter lockout status (see Section 4.2 Fault).

3.6 Preparing for System Operation

After the initial trip test has been accomplished, and the OSSD

safety outputs and EDM connections have been made to the

machine to be controlled, the EZ-SCREEN LP is ready for testing

in combination with the guarded machine.
The operation of the EZ-SCREEN LP with the guarded machine

must be verified before the combined EZ-SCREEN LP and

machine may be put into service. To do this, a Qualified Person

must perform the Commissioning Checkout Procedure

described in Section 6.2.

3.7 Sensor “Swapability” and Emitter Hookup

Figure 3-22 illustrates a hookup option that provides sensor

interchangeability (or “swapability”) – the ability to install either

sensor at either QD connection. This allows the emitter and

receiver positions to be easily swapped, similar to a popular

feature of Banner MACHINE-GUARD

, MINI-SCREEN

®

and

MICRO-SCREEN

®

safety light screens, providing advantages

during installation, wiring, and troubleshooting.
To use this option, connect all emitter wires in parallel (color-

for-color) to the receiver cable via individual wires or the CSB..

splitter cordset.

Advertising