ADS Environmental Services ADS Spider User Manual


Page 27

2.

ANALOG

type accepts an analog voltage from 0

2.5V.

The following diagrams show wiring details for most common
sensor types.

(i) 2-WIRE 0 - 20 mA and 4

20 mA current loop sensors

require an external 120-Ohm,

¼

W resistor (supplied):











(ii) 4-WIRE 0 - 20 mA and 4

20 mA current loop sensors

require an external 120-Ohm,

¼

W resistor













(iii) Voltage inputs may require up to two external resistors:






Sensor

+

+

-

-

Power
Supply

+

-

Spider system ground

Spider
IN X

120-Ohm

¼ W

Resistor

+

-

Sensor

+

-

Spider system ground

Spider
IN X

Ry

Rx

Sensor

+

+

-

Power
Supply

+

-

Spider system ground

Spider IN X

120-Ohm

¼ W

Resistor

+

-

Advertising