ADS Environmental Services ADS Spider User Manual


Page 38

Configuring Inputs


Decide how your inputs will connect to the Spider.

As described earlier in

Inputs

, every Spider input can be configured

in one of the following seven modes: switch closure (digital), analog,
counter, event, daily total, utility meter, or disabled.

Switch, counter, event, daily total, and utility meter inputs accept
simple ON/OFF sensors. Analog inputs accept a variety of
transducers, such as temperature sensors and water level sensors.

For example, you may want to monitor only 3 Inputs. The first two
may be switch (digital) types, monitoring operating status of two
pumps. The third may be an analog input monitoring a tank level.
Assume that

Pump status 1

will connect to Input 1,

Pump status 2

to Input 2, and

Tank level

to Input 3. The remaining 5 inputs will be

disabled.

If not already displayed, access the

CHANGE SETUP

page, as

described in Setting up a Spider for the First Time on page 32.

Click

Change Input Setup

.


Select

Switch

Input Type for the first two inputs and

Analog

for the

third. Select

Disabled

for the remaining five inputs. Enter

Pump

status 1

as the Input 1 Name,

Pump status 2

as the Input 2 Name,

and

Tank level

as the Input 3 Name.