Follow the step by step instructions.

NOTE: The two calibration points can represent any two values within
the transducer range. However, they must be at least half of the
transducer range apart.

You can exit at any time without making changes by clicking the

Cancel

link. Save the new values by clicking on the

Save

button.

Manual Calibration

User inputs are calculated with the following formula:

Calibrated value = Scaler x (Raw Value) + Offset


Manual calibration allows direct entry of the

Scaler

and

Offset

quantities. The same formula is used in the 2-point calibration. The 2-
point calibration procedure automatically calculates the

Scaler

and

the

Offset

.