ADS Environmental Services ADS Spider User Manual


Page 81

The Auto Acknowledge Time of 60 minutes ensures that
remote text message commands are not sent more often
than every 60 minutes, which could happen with water levels
that change quickly.

Using the same logic, setup another alarm on the local Spider to turn
the pump off. Its trigger should be Water level ABOVE 1 meter (39
inches) and the Message should be

Off rem3

, with all other settings

identical to the alarm described previously.

NOTES:

1. All alarm settings discussed above are only examples. You

will need to adjust these as appropriate for your application.

2. The transmitted text message commands are time stamped

and acted upon by the receiving Spider only if the reception
time is within 10 minutes of the command time stamp. This
minimizes the possibility of false commands caused by
network delays, text message delivery failures, etc.

3. Reception of all remote text message commands, whether

within the allowed period or not, is logged by the remote
Spider.














Remote control via text messaging is supported only if
both Spiders are fitted with software version 1.33 or
higher.

Remote control is supported only with the

On remx

,

Off remx

and

Pls remx

text message commands.


Attempting to use remote control with earlier software
versions or other commands may result in endless
loops, excessive text message transmissions, and very
large phone bills!