FGR2-PE Wirelss Data Transceiver

LUM0024AB Rev A

Options:

Any number of seconds.

Description:

Controls how long, in seconds, an incoming TCP connection must be idle (that
is, no data being transferred) before the transceiver drops the connection.

A setting of 0 means that the transceiver never disconnects an idle
connection—all disconnects need to come from the client.

Note: In some RTUs, after the RTU is connected to the transceiver as a
client, the RTU does not properly disconnect the TCP session. To help
overcome this potential behavior of some RTUs, FreeWave recommends
setting Inactivity Timeout to 10.

TCP Server Port

Web Parameter:

Port in the TCP Server Settings section of the Serial Setup page.

Network Type:

Both

Default Setting:

Blank

Options:

Any valid TCP port between 0 and 65535.

Description:

The TCP port the transceiver listens to for incoming TCP connections.

UDP Local IP Port

Web Parameter:

Local IP Port in the UDP Settings section of the Serial Setup page.

Network Type:

Both

Default Setting:

0000

Options:

Any valid IP port number between 0 and 65535.

Description:

The UDP port the transceiver listens to for connections when the
UDP/Multicast parameter is set to Enabled.

UDP Power Up IP

Web Parameter

Power UP Dest. IP & Port in the UDP Settings section of the Serial Setup
page.

Network Type:

Both

Default Setting:

0.0.0.0

Options:

Any valid multicast address from 224.0.0.0 to 239.255.255.255.

Description:

When the serial port is set to UDP mode, enter the IP address where the
transceiver sends any serial data coming into its serial port.

In the configuration Web pages, enter the IP address in the field to the left of
the colon. Enter the port number in the field to the right of the colon.