26 SCT Weight Transmitter Operator’s Manual

If the RS-485 network exceeds 100 metres in length or baud-rate
over 9600 are used, close the two jumpers, called "RS-485
termination", to activate two 120 ohm terminating resistors
between the ‘+’ and ‘–’ terminals of the line, on the terminal strip of
the furthest instrument. Should there be different instruments or
converters, refer to the specific manuals to determine whether it is
necessary to connect the above-mentioned resistors.

Direct Connection Between RS-485 And RS-232 Without Converter

Since a two-wire RS-485 output may be used directly on the RS-232 input of a

PC or remote display, it is possible to implement instrument connection to an RS-

232 port in the following manner:

This type of connection allows a SINGLE instrument to be used in a
ONE WAY mode.