Operation 35

Modbus Supported Functions

Among the commands available in the MODBUS-RTU protocol, only the

following are used to manage communication with the instruments. Other

commands may not be interpreted correctly and could generate errors or system

shut-downs:

The interrogation frequency is linked with the preset communication rate (the

instrument will stand by for at least 3 bytes before beginning to calculate a

possible response to the query). The dELAY parameter (see Section 2.4 “Analog

Output” on page 21) allows for a further delay in the instrument response, and

this directly influences the number of possible queries in the unit of time.
For additional information on this protocol, refer to the general technical

specification PI_MBUS_300. The functions supported relative to the MODBUS

standard are the READ HOLDING REGISTER and the PRESET MULTIPLE

REGISTERS.
In general, the query and response to and from a slave instrument are organized

as follows:

Function 3: Read Holding Registers (Programmable Register Reading)

Tot. bytes = 8

Tot. bytes = 3+2*No. registers+2

Function 16: Preset Multiple Registers (Multiple Register Writing)

Tot. bytes = 7+2*No. registers+2

Tot. bytes = 8

No. REGS: Number of registers to write beginning from the address.

FUNCTIONS

DESCRIPTION

03 (0x03)

Read Holding Register (Programmable Register Reading)

16 (0x10)

Preset Multiple Registers (Write Multiple DI Register)

QUERY

Address

Function

Add. Reg. 1

No. register

2 bytes

A

0x03

0x0000

0x0002

CRC

RESPONSE

Address

Function No. bytes Register1 Register 2

2 bytes

A

0x03

0x04

0x0064

0x00C8

CRC

QUERY

Address

Function

Add.

reg. 1 No. reg.

No.

bytes

Val.

reg.1

Val.

reg.2

2 bytes

A

0x10

0x0000 0x0002

0x04

0x0000 0x0000

CRC

RESPONSE

Address

Function

Add. Reg. 1

No. register

2 bytes

A

0x10

0x0000

0x0002

CRC