2-1 Installing Sensor Amplifiers

2

Inst
al

la

ti

on and

Conn

ect
ion

2-3

- Digital Fiber Sensor FS-N10 Series User's Manual -

• Contact your nearest KEYENCE office when connecting a unit

other than the N-bus (KEYENCE’s wire-saving system) compatible
sensor amplifier, including FS-N10 Series, or the NU Series com-
munication module.

• Turn the power off before connecting multiple expansion units.
• Do not touch the expansion connector with your bare hands.
• When using the FS-N10 Series as a main unit, use the products

within the expansion unit’s power voltage range if the power volt-
age range of the expansion unit is narrower than the FS-N10
Series.

1

Remove the protection covers from the main unit
and expansion unit(s).

2

Mount the main unit and expansion unit(s) on the
DIN rail.

3

Slide the main unit and expansion unit(s)
together. Engage the 2 claws of the expansion unit
with the recesses on the main unit side until you
hear/ feel a click.

4

Attach the separately sold end units (OP-26751: a
set of 2 units) to the DIN rail in the same manner
as step (2) (Tightening torque: 0.6N•m or less).

5

Secure the amplifiers between the end units.
Tighten the screws at the top (2 screws × 2 units)
with a Phillips screwdriver to fix the end units.

Point

Main unit

Expansion unit

(3)

(2)

(1)

End unit